Skip to end of metadata
Go to start of metadata

You are viewing an old version of this page. View the current version.

Compare with Current View Page History

« Previous Version 5 Next »

This page shows the pinout that has been pre-configured in the RapidConnect Lighting & Sensor firmware. For more details regarding peripheral compatibility or the hardware that is included with the RapidConnect Lighting & Sensor Evaluation Board, see the Application Circuit page.

Interface Summary

Digital In: PIR Occupancy Sensor, Ultrasonic Occupancy Sensor, Factory Reset Button

Analog In: Light Level Sensor

Digital Out: Network Status LED (PTI_DATA), Relay

Analog Out: PWM

Serial: UART TX, UART RX

Others: nReset, VCC, GND, JTDO, JTCK, JTD, JTMS, JRST, PTI_EN

Pinout Using Z357PA40-SMT Module

Notes:

  • All pins have maximum sourcing and sinking current of 4mA.
  • EM357 runs off a 3.3V 
  • (*) indicates ADC capable pin
  • (#) indicates PWM capable pin
Module PadFunctionRelation to zigbee FeaturesEM357 GPIO Hardware Integration Comments
1

PIR Digital In

When either of the two occupancy inputs are triggered (i.e. this pin or the Ultrasonic Digital In), the Occupancy Sensor Endpoint will update the value of the Occupancy Attribute in the Occupancy Sensing cluster.PC6 (13)
  • INPUT - Digital (Active Low)
  • Internal Pull-up
  • Requires Hardware Debounce
  • USAGE INSTRUCTIONS
2

Relay Out

When On/Off commands are sent to the Dimmable Light Endpoint, this output will turn on/off accordingly.PC7 (14)OUTPUT - Digital (Active High)
3

Reserved


PA7 (18)#Reserved for Future PWM
4VCC (3.3 VDC)


5nCTS / SPI Slave CLK
PB3 (19)#Reserved for Future PWM
6

nRTS / SPI Select (Host Controlled Handshake Line)


PB4 (20)#Reserved for Future PWM
7

nReset, active low


(12)
8

Network Status LED (PTI_EN)

Used as an indicator for two purposes:

Network Status

  • Joined: the LED will be SOLID.
  • Down: the application is never in the Network Down state, as it will persistently scan for a network if its not joined to one.
  • Scanning: the LED will BLINK.

Identify

  • On reception of an Identify command, the LED will BLINK for the specified Identify Time.
PA4 (26)*OUTPUT - Digital (Active High)
9

Reserved (PTI_DATA)


PA5 (27)*
10

JTDO


PC2 (33)
11

JTCK


(32)
12

JTD


PC3 (34)
13JTMS
PC4 (35)
14JRST
PC0 (40)
15

RXD


PB2 (31)UART Serial RX
16

PWM Out

When a Level Control command is received, the duty cycle of the PWM pin will be updated to match the intended Level (i.e. 0-100%).PA6 (29)#
  • OUTPUT - Digital (Active High)
  • 1k Hz Frequency
17

TXD


PB1 (30)UART Serial TX
18GND


19

Ultrasonic Digital In

When either of the two occupancy inputs are triggered (i.e. this pin or the PIR Digital In), the Occupancy Sensor Endpoint will inform the network that Occupancy is "true".PC1 (38)*
  • INPUT - Digital (Active Low)
  • Internal Pull-up
  • Requires Hardware Debounce
  • USAGE INSTRUCTIONS
20

Illuminance Analog In

The value conveyed via this analog input will be reported to the network by the Light Sensor.PB7 (41)*INPUT - Analog (0 - 1.2V)
21

Network Button

When this input is held low for >5 seconds, the application will execute a Factory Reset, leaving the network and clearing all settings.PB6 (42)*
  • INPUT - Digital (Active Low)
  • Internal Pull-up
  • Requires Hardware Debounce
  • Hold low for >5 seconds to initiate Factory Reset
  • No labels